Technical Data | Rated Voltage | UN / [VAC] 400/480, 600/690 | Max. Voltage | Umax / [VAC] 690 | Rated Frequency | fN / [Hz] 50/60 | Rated Currents | IN / [AAC] 3...1200 | Thermal Current | Ith / [ARMS] 1,07 x IN | Test Voltage | U / [VAC] 3000 (1 min) | Rated Impedance | 3/4/5% @ 400VAC 50 Hz / 480V/60Hz, 600V/60Hz | Overload | 1,5 x IN for 1 min/h | Impregnation | Vacuum-overpressure (VPI) | Insulation Class | T50/H, 115C rise | Type of Cooling | Natural convection (AN) | Protection Class | IP00 | | Advantages of MANGOLDT ACL chokes at a Glance: - 5-in-1 functions as line/load choke, SCR Notch choke, PWM choke, dv/dt choke
- Featuring Mangoldt’s PolyGap® core construction for low harmonic (and PWM) losses
- High linearity inductance for maximum absorption of transients
- Cost-effective solution to reduce harmonic distortion
- Increased reliability and lifetime of the inverter (VFD)
- Improved overall performance
- Standard winding in aluminium (competitive raw material costs and less weight) - on request also in copper
- Direct availability: stock in Germany, USA and Canada (partners)
- All chokes are UL listed
|